Estimating supply airflow from a room’s sensible cooling load
A sensible-heat calculation links a room’s temperature load to the amount of supply air needed at an assumed temperature difference. It is a useful check when reviewing an airflow schedule, provided the temperature and moisture questions are kept distinct.

Calculate an illustrative room
Assume 6 kW of sensible load, an air density of 1.2 kg/m³, specific heat of 1.0 kJ/(kg·K) and a 10 K room-to-supply temperature difference. Using Q = ρ × cp × V × ΔT, the volume flow is 6 ÷ (1.2 × 1.0 × 10) = 0.50 m³/s, or 500 L/s.
Check what happens at a warmer supply temperature
With the same load and an 8 K difference, the result becomes 0.625 m³/s. That change affects branch sizes and terminal selection. Use temperatures at the appropriate points: the air delivered to the room may differ from air leaving the coil after fan heat and duct gains.
What does the calculation leave out?
The result addresses sensible room heat under the stated assumptions. Humidity control, outdoor-air provision, control strategy and part-load operation need their own checks. Record the assumed temperatures beside the design flow so a reviewer can reproduce the arithmetic.
Check the boundary on a site visit
The room sensor measures a condition at one location, while a supply temperature might be recorded at the unit or at the terminal. Write down both measurement locations and the time. If a branch crosses a hot service space after leaving the unit, the temperature at delivery can differ. In a hand check, a larger assumed difference produces a smaller airflow. That makes the temperature assumption just as important to report as the numerical result.