Finding the index run in a duct pressure calculation

The branch that needs the most fan pressure is not necessarily the longest line on the plan. Fittings, terminals and equipment can make a shorter route more demanding. Build a pressure budget for each candidate path using one consistent pressure convention.

ARAD workshop reference · press work
ARAD workshop reference · press work

Compare two candidate paths

In a simplified example, route A has 24 Pa of straight-duct loss, 18 Pa of fitting loss and 25 Pa at its terminal. Its total is 67 Pa. Route B has only 15 Pa of straight loss, but 35 Pa at fittings and 22 Pa at the terminal. At 72 Pa, B governs this comparison.

Trace the shared components once per path

A common upstream filter or coil can belong to both routes. Add its design loss once to each full path if it lies within the pressure boundary under review. Do not add the totals of parallel branches. Pressure losses along a path add; the design flow at a junction follows a different calculation.

What should accompany the result?

Label the start and end points, flow through each section and source of every fitting or equipment loss. Before selecting a fan, confirm the manufacturer’s pressure convention and the applicable system effects. A transparent route schedule makes later substitutions much easier to check.

How a drawing revision changes the answer

An extra elbow on the lower-loss route can change which branch governs. Keep the losses split into straight sections, individual fittings and scheduled components, so that a revised path can be recalculated without rebuilding the entire sheet. Compare both routes again at their revised design flows. The governing path is a result of the current design; a label copied from an earlier drawing is not evidence that it remains the governing path.